CCEF's measures sheet for Xcel-area contractors lists the heat pumps ClearPath can finance. A standard heat pump has to meet three efficiency lines. A cold-climate heat pump has its own lines, plus two tests at 5°F.
| Rating | Standard | Cold-climate, ducted | Cold-climate, ductless |
|---|---|---|---|
| SEER2 | 15.2 | 15.2 | 16 |
| EER2 | 11.7 | 11.7 | 9 |
| HSPF2 | 7.8 | 8.1 | 9.5 |
| COP at 5°F | none | 1.75 | 1.75 |
| Capacity at 5°F (share of 47°F) | none | 70% | 70% |
Sources: CCEF's "Eligible Program Measures for Xcel Energy Contractors" sheet for the first three rows; CCEF's contractor portal and Xcel's cold-climate rebate for the 5°F rows. Sheet checked October 14, 2026; portal and rebate summary October 13.
SEER2 is cooling efficiency over a season, EER2 cooling on a 95°F afternoon, HSPF2 heating over a season. COP at 5°F is heat out per unit of electricity in at full output. Capacity at 5°F is the heat output at 5°F as a share of the 47°F rating.
Where CCEF's documents differ
For a ducted cold-climate heat pump, CCEF's contractor portal accepts an EER2 of 10 and the measures sheet says 11.7. A ducted system between the two goes to CCEF to confirm before you approve the estimate. The checker marks it that way and never calls it a pass.
Why 5°F matters in Denver
Denver's heating design temperature is close to 0°F, and an average Denver winter has about 74 hours below 5°F (NOAA's hourly readings at Denver International Airport, counted over the ten winters from the 2015-16 season through the 2024-25 season). The two 5°F ratings show how much heat the unit still makes on those mornings, and how efficiently. A COP of 1.75 means 1.75 units of heat for each unit of electricity, still well ahead of electric resistance heat at 1.0.
Xcel's cold-climate rebate
Xcel asks for 15.2 SEER2, 10 EER2 and 8.1 HSPF2 on ducted and mixed systems, and 16, 9 and 9.5 on ductless, with the same 5°F tests. It pays per heating ton at 5°F. A standard heat pump can go on ClearPath and still miss this rebate.
Ground-source heat pumps
CCEF's sheet lists them at 16 EER2 and a full-load COP of 3.3. The checker covers air-source heat pumps only.
Where the numbers are
SEER2, EER2, HSPF2 and the 47°F capacity are on the AHRI certificate. The 5°F numbers are on NEEP's cold-climate list and the spec sheet. The AHRI guide shows where each one sits.
Common questions
Does a SEER rating without the 2 count?
Use SEER2. SEER2 and HSPF2 come from the newer federal test; SEER and HSPF come from the older one, and the numbers don't compare.
Does a heat pump water heater have to meet these?
No. These are for heat pumps that heat and cool the house. A heat pump water heater needs to be ENERGY STAR rated.